What causes a thermostat of an electric water heater to have to be reset?
The element is about to completely go out.
Could be just the thermostat, but if the element is pulling more than 22 amps, I replace them to stop a second callout a few weeks later.
EDIT: Just read the rest of your question.
The two times I had that, it was a pinched wire going to the lower thermostat.
Found both after callbacks by pulling on the wires.
On one of the heaters, the wire pulled in two at the spot it was getting hot. It was just about to burn completely in two.
Do this check with the power off btw.
What causes a thermostat of an electric water heater to have to be reset?
if it has two adjustable thermostats then make sure the over heat one is set higher, say 60 for the operating one and about 70 for the overheat
defective lower t-stat. I have had that problem multiple times.